Product Code: 168-543

Redline Plus XDI-F1-CA-IR Flammable Hydrocarbon (0-100% LEL)

The GDS Red Line XDI sensor uses proven non-dispersive single beam dual-wave length infrared principles to detect and monitor the presence of gases. This non-poisoning sensing technique relies on the target gas having a unique well-defined absorption signature. This is used to identify the presence of the target gas and is highly specific. Using a suitable infrared source, an analysis of the optical absorption through the gas allows the concentration of the target gas to be determined.

All sensor driving is internal to the transmitter and full fault monitoring of the sensor and transmitter is continuous.

Specifications


GENERAL DATA
This information relates to the device operating continuously.

Hydrocarbon Sensor
Operation - continuous diffusion NDIR (duel wave-length)
Measuring Range - Standard 0~100% LEL 0~100% Vol
Others available
Accuracy - 5% F.S.D
Warm up time to zero < 20 seconds
Response time to target gas T90 < 35 seconds
Long term zero drift - 5% F.S.D
The 4~20mA output provides a fault indication by reducing the output to below 2mA,
with the recovery from fault condition being automatic.


ELECTRICAL DATA
Input voltage - 3 wire device
18 to 35V DC - 24v DC nominal
(polarity protected)
Output - 4~20mA (selectable as sink or source)
Fail signal - 4~20mA reduced to 2mA
Maximum current consumption - 130mA
Maximum loop resistance in source mode - 250R
Resolution - 0.15% of span
Output resolution - 0.02mA
Maximum offset drift - 20uA
Relays Optional - Low / high / fault alarms S.P.C.O. 0.5A @30v DC


MECHANICAL DATA
Certification
Explosion proof ATEX-IECEX
II2G Exd IIC T6-T3 Gb
II2D Extb IIIC T85-C Db
Replaceable plug in sensor - In-situe
Sensor accessory mounting thread - 33mm - 1.25 pitch - 6 full threads
Enclosure - Type XDI - Aluminium alloy - optional stainless steel
Gas Sensor - Type F1 - Stainless steel - 316 S16
Weight - 3.95Kg
Cable Entry - One - 20 mm 1.5 pitch / Options 25 mm - 3/4 NPT
Mounting Detail - Two M5 (126 mm CRS)
Approximate dimensions-terminal enclosure - 126 mm dia. 83 mm deep
Environmental Data - IP64 + Water Shield IP65
Operating Conditions - 0 ~100% RH (non-condensing) / -15 ~ +55?C
Storage Conditions - 0~99% RH non-condensing / -20 ~ +60?C


ACCESSORIES:
Collector Cone + universal fitting
Universal Fitting (Test Gas Applicator Spray Deflector)
Flow Block - nylatron
Flow Block - stainless steel
Water Shield - stainless steel
Duct Mount Kit
Detector head Weather Shield
F1 sensor Thermal Jacket

Downloads

Select a variation from the product list

Buy for: £996.99 (ex VAT)
Buy for: £1,196.39 (inc VAT)
 

Shawcity offer technical support on all products.
For more information call 01367 899553.

Register for a Shawcity account

  • Manage your quotations and track order progress
  • Store your contact and delivery information for easy check-out
  • Use the ‘Add to favourites’ feature to make reordering simple.

SIGN UP TO OUR NEWSLETTER

Shawcity will only use your email address for the purpose of sending you news and product updates.
We will not share your details with any other party. You can stop receiving our communications at any time,
by clicking on ‘Unsubscribe’ within our emails or by contacting: marketing@shawcity.co.uk.

ATEX is the name commonly given to the two European Directives for controlling explosive atmospheres.

ATEX certification ensures that equipment is fit for use within explosive atmospheres and is supplied with adequate information to ensure it can be used safely.

For more information visit: hse.gov.uk/fireandexplosion/atex.htm